前室微压差传感器根据消防要求加压送风时应使防烟楼梯间压力、前室压力、走道压力、房间压力,同时还要保证各部分之间的压差不要过大,造成开门困难影响疏散。当火灾发生时,机械加压送风系统应能够及时开启,防止烟气侵入作为疏散通道的走廊、楼梯间及其前室,以确保有一个、畅通无阻的疏散通道和环境,为安全疏散提供足够的时间逃生,本公司生产的HLB-016压力传感完全可以满足消防规定要求
前室压力探测器消防前室
消防前室压力传感器接线
前室微压差传感器
根据消防要求加压送风时应使防烟楼梯间压力、前室压力、走道压力、房间压力,同时还要保证各部分之间的压差不要过大,造成开门困难影响疏散。当火灾发生时,机械加压送风系统应能够及时开启,防止烟气侵入作为疏散通道的走廊、楼梯间及其前室,以确保有一个、畅通无阻的疏散通道和环境,为安全疏散提供足够的时间逃生,本公司生产的HLB-016压力传感完全可以满足消防规定要求
前室压力探测器消防前室压力传感器接线
When the supply air volume and time of itive pressure air supply system is out of control, the normal escape route may be too high because of the itive pressure of the front room, the fire door can not open the serious cequences. In view of the above ciderati, the Sichuan Institute of Fire Science combined with experience to provide data of residual pressure value. By controlling the opening and closing of the by-pass Valve, the differential control system can effectively control the residual pressure of the mechanical pressurized air supply system within the reasonable range required by the national standard ——40-50 PA in the smoke-proof Stairwell, the front room, the shared front room, the front room of the fire elevator room and the enclosed refuge floor (room) are 25-30Pa.

压力传感器控制箱消防前室压力传感器接线
通用型压差控制器广泛应用于前室(合用前室)压差测控系统、封闭避难层、防烟楼梯间压差测控系统;室内外压差检测、过滤网堵塞监控系统等干燥气体的压差测控系统。
特点:
◆带一个绿色巡检指示灯,一个红色报警指示灯;◆直接输出开关控制信号;◆供电及信号输出采用总线制传输;
产品参数:
量 程:0~100Pa 控制器寿命: 10万次
耐 压:1000Pa 电气等级: 24 VDC/0.3A
动作压力: 切 换 率: 大6次/分钟
前室/走道:25~30Pa,(复位压力:15~20Pa); 外形尺寸:172*112*60

电梯前室压力传感器消防前室压力传感器接线
正压送风压力传感器,正压送风口压力传感器,电梯前室压力传感器,楼梯间压力传感器,电梯前室出风口压力传感器,楼宇楼房正压送风压力传感器,旁通阀泄压压力传感器,正压送风系统压力传感器,带显示正压送风口压力传感器pressure air supply pressure sensor, itive pressure air supply outlet pressure sensor, Elevator Chamber pressure sensor, Stairwell Pressure Sensor, elevator chamber outlet pressure sensor, building itive pressure air supply pressure sensor, pressure Relief by-pass Valve pressure sensor, itive pressure air supply system pressure sensor, with display itive pressure air supply outlet pressure sensor
-->