TECHNICAL DATA
Heating element PTC resistor - temperature limiting
Temperature safety cut-out to protect against overheating in case of fan failure,
automatic reset
Axial fan, ball bearing airflow see table
service life 50,000h at +25°C +77°F
Connection 2-pole clamp 2.5mm2, clamping torque 0.8Nm max
Casing plastic according to UL94 V-0, light grey
Optical indicator thermostat control lamp
Mounting clip for 35mm DIN rail, EN 60715
Fitting position vertical airflow air outlet up – other fitting positions possible
Dimensions 100 x 128 x 165mm
Operating/Storage temperature -45 to +70°C -49 to +158°F
Operating/Storage humidity max. 90% RH non-condensing
Protection type/Protection class IP20 / II double insulated
Approvals VDE, UL File No. E204590, GOST TR
Art. No. Operating voltage Heating capacity1 50Hz Heatig capacity1 60Hz Inrush current max. Pre-fuse T time-delay Airflow, free flow Setting range thermostat2 Weight approx.
02700.0-00 220-240VAC, 50/60Hz 475W 550W 11A 6.3A 35m3/h 0 to +60°C 0.9kg
02701.0-00 220-240VAC, 50/60Hz 550W 650W 13A 8A 45m3/h 0 to +60°C 1.1kg
02700.9-00 100-120VAC, 50/60Hz 400W 550W 14A 8A 35m3/h +32 to +140°F 0.9kg
02701.9-00 100-120VAC, 50/60Hz 510W 650W 15A 8A 45m3/h +32 to +140°F 1.1kg
1 at +20°C +68°F ambient temperature 2 Switch temperature difference 7K ±4K tolerance